Abstract
Microgrids (MGs) and distributed renewable energy sources (RESs) have been widely used in Australian agriculture. Because of the irrigation characteristics of cotton plants and the intermittent power generation of RES, the cotton farm MG design problem has become challenging. To optimally design the renewable energy systems of cotton farm MGs, one should consider the energy cost of cotton irrigation, total investment cost and simple payback period simultaneously. This paper proposes an optimization model for the cotton farm MG design, which can identify the best RESs and energy storage configuration to meet the irrigation demand. In addition, the designed MG uses solar photovoltaic units and wind turbine generators as RES, which are further aided by battery storage to maintain energy supply at the least cost. The objectives of MG design include minimization of operation cost, investment cost and a simple payback period, which is formulated as a normalized multi-objective function.
Similar content being viewed by others
Avoid common mistakes on your manuscript.
Introduction
As one of the largest exporters in rural areas, the cotton industry in Australia creates thousands of jobs every year [1]. With more than 427 thousand hectares used to plant cotton among over 1400 cotton farms, the overall revenue in the cotton industry hit a record of AU$ 2.3 billion in 2017/2018 [2]. As an industry with high energy demand, the revenue of the cotton industry is highly sensitive to energy costs. Therefore, reducing operating costs plays an important role in improving the competitiveness of Australian cotton products. This paper aims to reduce cotton farm energy costs by designing the relevant microgrid (MG) equipped with photovoltaic (PV) units, wind turbines (WT) generators, and battery storage. In order to design a more suitable MG for cotton farms, this paper takes operation cost, investment cost and simple payback period as the optimization objectives, and the constraints of the cotton farm such as seasonal irrigation demand, water reservoir, water evaporation, etc. In our preliminary study in [3], a grid-connected MG model is established for a cotton farm pum** system, and a case study was carried out to validate the proposed model. This paper is a further study of our preliminary study in [3], and the multi-objective model is normalized to stabilize the weighting factors to facilitate sensitivity analysis on various key impacting factors.
The Australian cotton farming region is rich in natural resources. The yearly average solar global horizontal irradiation is 4.86 kWh/(m\(^2 \cdot \) day), the annual average wind speed at 50 m height is 4.2 m/s, and the annual average temperature is 16.04 °C. In the literature, many studies on renewable energy generation have been proposed in agricultural areas. For example, Ref. [4] illustrates a standalone MG case study in which a hybrid power supply system was implemented in a cotton farm at Emerald, Queensland, and the optimal design of irrigation pumps in a cotton farm was achieved by the software Hybrid Optimization of Multiple Energy Resources (HOMER). In [5], an off-grid MG is investigated for a cotton farm in Australia, and HOMER was used to obtain the optimal investment results for energy cost reduction. In the case study of [6], thirteen hybrid MG projects are evaluated, and a sustainability assessment is performed in terms of the institutional, technical, environmental, and social-economic impact on rural Venezuela. Furthermore, rural MGs can be divided into two categories as per operation mode: grid-connected and off-grid MGs [7]. Several papers present an off-grid MG system based on renewable energy sources (RESs) and conventional energy sources. Ref. [8] develops a viable MG system including PV, small hydro, battery storage, and diesel generators for rural electrification in Southern Cameroons. Ref. [9] proposes a methodology based on the energy balance evaluation for a given design period to determine the size of the electrical energy storage in standalone systems. In [10], a hybrid AC/DC off-grid MG planning model is proposed to help select the best technology for each device from the candidate list.
Grid-connected MGs are often applied in rural areas. For example, a grid-connected hybrid MG with PV and wind turbine is reported in [11], which can meet the energy needs of 15 residential houses in rural communities in Chile. A grid-connected MG is recently established in a remote area of Uttar Pradesh, India, and the installed PV and battery storage can support the loads in case of insufficient power from the grid [12]. These MG design results are not directly applicable to the MG of cotton farms because of the seasonal energy demand of water pum**: water needs to be pumped only during irrigation periods, and there is not any water pum** load at non-irrigation periods. Due to this extraordinary characteristic, the scale of the designed MG needs to be appropriately decided for the cotton farm: A MG of a too large size increases the capital cost, while an MG of a too small size leads to instability issues and does not contribute significantly to reducing the operational cost. To solve the aforementioned issue, this paper will study the optimal sizing problem of a cotton farm MG tailored to the irrigation characteristics of cotton farms. Furthermore, the charge from the grid for the maximum demand will be modelled to match the actual situation of the Australian cotton industry [13]. In literature, many existing studies minimise energy costs under the time-of-use (TOU) electricity tariff and charge for the maximum demand. For example, an optimal load shifting strategy is presented in [15] to reduce the TOU cost and maximum demand charges for a water pum** system. Moreover, a multi-agent mathematical model is presented in [16] for energy cost reduction through demand-side management. The results show that the proposed method can significantly reduce domestic energy consumption. A demand-side management model is introduced in [17] for an MG equipped with PV and battery storage to reduce residential energy costs.
However, it is difficult to shift the irrigation pump load for cotton farms, especially in the water high-demand season in which cotton needs to be irrigated continuously for at least two to three weeks, and the pumps are kept running for these weeks. To resolve this issue, the most common method is reducing the maximum demand cost by energy storage, which can be considered for power management and peak demand reduction in the grid-connected MG system. Ref. [18] shows that battery size optimization can ensure a smooth power flow in the MG and reduce peak load demand. [19] takes advantage of the particle swarm optimization method to minimize the MG’s total energy and operating cost by optimally adjusting the control variables to satisfy various constraints. Ref. [20] reviews the control strategies of different types of energy storage devices and the corresponding working principles and limitations. Consequently, battery storage can be considered for power management and peak demand reduction in the grid-connected MG system in [21]. By 2025, Australia will have over 15,800 cotton farms and other agricultural consumers connected to the electricity grid [4]. Therefore, the choice of electricity price plays a critical role in shortening the investment payback period for a grid-connected MG. An electricity cost reduction demand side management model based on MG supply chain and TOU tariff is proposed by [22], where end-users are equipped with energy storage. A model is developed in [23] to evaluate the effectiveness of demand response strategies using TOU tariff combined with regional thermal control. Ref. [24] proposes a model to reduce residential electricity demand by considering price elasticity and solar PV power, where Monte Carlo simulation for power flow analysis in low-voltage distribution networks was applied. However, these models have not considered the situation in that power utility purchases energy from MGs. A feed-in tariff (FIT) is one of the incentive schemes envisaged by the Australian government for RES installation. Nevertheless, Australia’s Small-scale Renewable Energy Scheme (SRES) limits PV installation to no more than 100 kW and wind systems to a capacity of no more than 10 kW. In this study, the FIT scheme is considered in the objective function to reduce operational costs. Meanwhile, FIT can shorten the payback period for the grid-connected MG during off-irrigation seasons.
For the MG optimization modelling, Ref. [25] develops a model for energy storage management in the distribution network, which can reduce operational costs and improve voltage stability. A stochastic techno-economic MG model is proposed in [26] for a rural MG to assess technical design decisions and financial conditions. Ref. [27] models a hybrid energy system and obtains the optimal configuration with the help of life cycle cost minimization. Furthermore, Ref. [28] establishes a pump storage model based on the hybrid solar-wind system to do the techno-economic optimization for a rural MG.
The aforementioned literature paid attention to the RES integration and management method for rural MGs, but none of them discussed the case that both seasonal pum** loads and intermittent renewable sources appear simultaneously in the same MG. Motivated by the problems mentioned above, this paper presents a new cotton farm MG design method, where the seasonal water pum** demand and intermittent PV and wind power generation are considered. The proposed cotton farm MG is structured with PV, WT, and battery storage. In addition, the proposed MG is assumed to be connected to the power grid to ensure enough power supply for irrigation. PV and wind turbines are energy generators in this MG, and the battery is essential for energy demand management under time-varying FIT. However, the corresponding investment cost is expensive and should not be ignored. Considering all these factors, this study proposes a multi-objective optimization problem to minimize MG’s operational cost, investment cost, and payback period. A grid-connected MG cotton farm case study is simulated to validate the design results. Furthermore, the impact of numerical research results in different situations is considered from the perspective of cotton farm stakeholders.
The main contributions of this study are given below.
-
(1)
A multi-objective MG optimal design model is proposed for cotton farms that are able to handle seasonal water pum** loads under various weather conditions, Australia’s renewable energy policies, electricity prices, and FITs.
-
(2)
The relationships among pump energy consumption, water storage and irrigation water demand during cotton planting cycles are modelled in the MG design.
-
(3)
Using an actual cotton farm for the case study, the impact of grid electricity tariff and FIT on the initial investment and routine operational costs of the MG is discussed. The case study also indicates that the capacity of the WT should be limited by 10 kW in order to be economically viable.
The rest part of this paper is organized as follows. Section 2 introduces the RES components of MG for Australian cotton farms and establishes design objectives and constraints of RESs and cotton irrigation. Details of a case study are given in Section 3. In Section 4, the Yalmip toolbox [29] is used together with MATLAB fmincon optimization tools to solve the normalized multi-objective MG optimization problem. The numerical results and the economic impact are also discussed in this section. Section 5 summarizes the paper and draws conclusions.
Optimal design of cotton farm microgrid
In this section, the energy models of key MG components are briefly reviewed.
Figure 1 shows the power balance within the MG. The power of water pumps is supplied by the grid, battery storage, PV and WT. In Fig. 1, notation \(P_g(t)\) represents the amount of power purchased from the grid at time t, i.e., the \(t^{th}\) hour since the time is sampled each hour; \(P_{m1}(t)\) is the power flowing from the PV and WT to the water pump at time t; \(P_{b1}(t)\) denotes the power discharged by the battery at time t to supply the load. Excess power from the PV and WT can be sold to the grid or charged to the battery storage. The notation \(P_{m2}(t)\) denotes the power flowing from the PV and WT to the battery storage at time t, and \(P_{m3}(t)\) denotes the excess power from the PV and WT to the grid. When water pumps are not switched on, the battery also can sell power (denoted by \(P_{b2} (t)\)) to the grid to make a profit. The power flows in this diagram are functions of time t. Hourly samples are taken in the models, and each year consists of 8760 hours. The water irrigation system of the cotton farm is illustrated in Fig. 2. To meet the water irrigation demand, pumps lift water from the bore or river through ditches to turkey nest dams. Then the water will flow from the dams to cotton farms by gravity. In Fig. 2, notation \(P_{(pump,k)}(t)\) represents the nominal power of the \(k^{th}\) pump at time t; and \(F_0(t)\) denotes the water flow rate from the dam to the cotton field at time t.
Objective functions
From the system configuration in Fig. 1, the following equations can express the MG design objective functions.
In Eq. (1), \(f_{op}\) represents the annual operational cost of the MG, \(\beta _1(t)\) denotes the grid electricity price at time t, \(T=8760\) is the number of hours in a year, \(\beta _2(t)\) is the FIT rate at time t (AU$ /kWh), and \(C_0\) represents the annual maintenance cost of the MG. Eq. (2) calculates the capital investment cost of the MG, where there are L, M, and N different types of PV panels, WTs and battery storage, respectively. Notations \(k_{1p}\), \(m_{1p}\), and \(x_{1p}\) are the unit price (in AU$ /kW), rated power (in kW), and the total number of installed panels of the \(p^{th}\) type of PV, respectively. Symbols \(k_{2q}\), \(m_{2q}\), and \(x_{2q}\) represent the unit price (in AU$ /kW), rated power (in kW), and the number of installed units of the \(q^{th}\) type of WT, respectively. Similarly, \(k_{3r}\), \(m_{3r}\), and \(x_{3r}\) are the unit price (in AU$ /kWh), single unit battery capacity (in kWh), and the total number of installed battery units of the \(r^{th}\) type of battery storage unit. Since \(x_{1p}\), \(x_{2q}\) and \(x_{3r}\) represent the MG equipment quantity, they need to satisfy integer constraints. Eq. (3) gives the simple payback period (\(f_{payback}\)), in which \(C_{org}\) denotes the baseline annual operation cost before the installation of the MG. The multi-objective functions in Eqs. (1-3) can be transformed into a single objective function in Eq. (4) by weighting factors \(\lambda _1\), \(\lambda _2\), and \(\lambda _3\). However, these objective functions have different magnitudes, so it is convenient to normalize the objectives to obtain an optimal solution consistent with the weighting factor specified by the decision-maker. Therefore, a weighted summation normalization method is adopted to Eqs. (8) - (13). These objectives are normalized by using the true variation intervals of the objective functions on the Pareto optimal set, and \(f_{op}^{norm}\), \(f_{invest}^{norm}\) and \(f_{payback}^{norm}\) represent the normalized \(f_{op}\), \(f_{invest}\) and \(f_{payback}\), respectively; \(f_{op}^{min}\), \(f_{invest}^{min}\) and \(f_{payback}^{min}\) are the Utopia points satisfying \(f_{op}^{min}\) = \(f_{invest}^{min}\) = \(f_{payback}^{min}\) = 0; and \(f_{op}^{max}\), \(f_{invest}^{max}\) and \(f_{payback}^{max}\) are the Nadir points of the individual objectives, in which \(f_{op}^{max}\) is based on the maximum energy to be purchased to satisfy the irrigation demand; \(f_{invest}^{max}\) and \(f_{payback}^{max}\) are based on the farm owner maximum investment and payback willingness. Yalmip toolbox is used to solve this optimization problem. The weighting factors \(\lambda _1\), \(\lambda _2\), and \(\lambda _3\) satisfy constraints in Eqs. (8), (9) - (11) are the constraints to ensure all the objective functions satisfy the farm owner’s requirement.
System constraints
According to the power flow in Fig. 1, Eq. (12) shows that the pump load is supplied by PV, battery storage and utility, while Eq. (13) shows the power balance from PV and WT:
where:
-
sep=0pt
-
\(P_p(t)\) is the total power of water pumps at time t;
-
\(P_{PV}(t)\) is the power from the PV at time t; and
-
\(P_{WT}(t)\) is power from the WT at time t.
Battery storage constraints
The state-of-charge (SOC) of the battery storage satisfies the following relation Eq. (14) derived from energy balance and is also subject to the boundary constraints in Eq. (15).
where:
-
sep=0pt
-
\(S_{soc}\) (t) is the SOC at time t;
-
\(S_{soc}^{min}\) is the minimum bound of SOC and is chosen as 20% in the case study; and
-
\(S_{soc}^{max}\) is the maximum bound of SOC and is taken as 90% in the case study.
Grid feed-in constraints
When the MG is in grid-connected mode, the feed-in power satisfies the following constraints in Eq. (16)
where \(Q_1\) denotes the allowed maximum power for grid feed-in.
PV constraints
The power generated from the PV satisfies the following constraints:
where \(P_{PV,p}^0(t)\) denotes the PV power generation per panel at time t.
Wind generation constraints
Power generated by the WTs satisfies the following relations:
where \(P_{WT, q}^{0} (t)\) is the power from a type q WT at time t. Eq. (21) represents that the total WT capacity installed should be less than 10 kW, which is the maximum power of any small-scale wind system allowed by the Australian government [30].
Water storage constraints
Assume that variable speed drives to control the water pumps, then the water storage reservoir satisfies the following constraints in Eqs. (22) - (27):
where:
-
sep=0pt
-
\(S_{min}\) is the minimum amount of water in the reservoir (ML);
-
\(S_{max}\) is the maximum allowed water volume of the reservoir (ML);
-
S(t) is the amount of water volume in the reservoir at the \(t^{th}\) hour (ML);
-
\(P_{pump,k}^{rated}\) is the rated power of the \(k^{th}\) pump (kW);
-
\(M_k\) is the average amount of water that each kW of input power at the \(k^{th}\) pump can raise from the water source (e.g. river) to the reservoir (in ML/kW). That is, this \(P_{pump,k}(t) \cdot M_k\) mega litre of water will be pumped from the water source to the reservoir once the \(k^{th}\) pump is run at its rated power, and this value depends on the water head from the water source to the reservoir;
-
D is the annual water demand for cotton irrigation (ML/Ha);
-
A is the size of the irrigated cotton farm (m\(^2\));
-
\(T_1\) is the total irrigation hours in a year (Hours);
-
\(V_L (t)\) is the loss of water from evaporation and seepage at time t, and \(V_L (t)\) is calculated by Eq. (24);
-
\(\delta \) is the on-farm water use efficiency during the irrigation period [31]; \(\delta \)=80% in this study [32];
-
n is the total number of pumps; and
-
\(R_0 (t)\) is average rainfall at the \(t^{th}\) hour (ML). As a source of supplementary water, the ratio of annual rainfall to irrigation water can be obtained from CRDC publications. For example, the rainfall in 2016 was approximately 33% of total irrigation [33].
Case study
Basic information
In Australia, the average amount of requested water of a cotton field is \(6.8 \times 10^{-4}\) megalitres (ML) per square meter, and the average area of a cotton farm is \(3.05 \times 10^6\) square meters [2] in the last decades. The cotton farm considered in this case study is in the southern part of Gunnedah, New South Wales, and its irrigation area in 2016 was \(3 \times 10^6\) m\(^2\) [34, 35]. There are three sub-bore pumps in this farm, which are powered by electricity, two with the rated power of 75 kW, and one with 37 kW [34]. The farm reservoir has a maximum water storage capacity of 1500 ML. The cotton farm parameters in this study are shown in Table 1. The water demand data are taken from the average water usage of cotton farms in the Murray-Darling Basin area in 2016, which includes the rainfall as a supplementary water source accounting for about 33% [33] of the total irrigation demand. The historical solar radiation data for the Gunnedah area in 2016 can be found in [36]. Currently, no MG is installed in the farm, and the corresponding baseline annual energy consumption and total cost of the three water pumps are shown in Table 2, where Ergon Energy small-business flat rate Tariff 20 is applied. Table 3 calculates the corresponding operational costs under a different tariff, i.e., the Ergon Energy rural TOU Tariff 65. The FIT has two different schemes: a time-varying and a flat oneFootnote 1, see Table 4. The energy consumption of three pumps in a year is shown in Fig. 3.
Microgrid components and costs
Table 5 shows the specifications of the PV panel considered in the case study. Table 6 lists information regarding three different sizes of WTs on the Australian market, and Fig. 4 displays the average annual energy generation of the three types of WTs. Table 7 shows popular battery storage products from Tesla® and the corresponding data [37].
Results and discussion
This case study is aimed at validating the proposed MG model. We consider deterministic algorithms for effectively leveraging historical data to optimize the configuration of RESs, utilizing the inherent advantage of high efficiency. Consequently, a deterministic algorithm is employed in this study. Note that the deterministic algorithm SQP is very sensitive when constraints are expressed as equalities. Therefore, we have modified the related constraints in the coding, replacing the equalities \((A=B)\) with inequalities (\(-\varepsilon< A-B < \varepsilon \)), where \(\varepsilon \) is a near-zero positive number. The results are discussed in the next three subsections below. The multi-objective optimization model is normalized, and the Yalmip optimization solver is applied together with the MATLAB fmincon toolbox to obtain the results. Table 8 shows the Baseline Case conditions of the studied cotton farm. The historical data of the water pump energy consumption in 2016 is used in the case study as a baseline for comparison. Figure 5 show the annual power generation of 2kW, 5kW and 10kW wind generators at the height of 10-15 meters, where the annual average wind speed is 3.4 m/s. Figure 6 shows the energy generated by a 1kW PV panel in the Gunnedah area in 2016.
Optimal microgrid design solution
Now consider the MG optimal design model in Section 3. The PV panel parameters are given in Table 5; the rated power of each PV panel is 253 W. The 2 kW, 5 kW and 10 kW WTs from Table 6 are available choices. The lithium-ion battery pack in Table 7 is used for the battery storage system, and each pack is rated as 13.5 kWh. Because the installation of the WT must comply with the Australian small renewable energy scheme, the total installed WT cannot be greater than 10 kW.
Figure 7 shows the changes of dam water volume. This curve is drawn based on the power consumption of pumps during the watering period in the cotton farm, rainfall and water loss. The total amount of water pumped, irrigation water usage, supplementary rainfall, and water loss must meet the maximum dam capacity and irrigation demand. It can be seen from Fig. 7 that when the irrigation demand is 6.5 x 10\(^{-4}\)ML/m\(^2\), the minimum water volume is 425.6 ML during the irrigation time, the maximum water volume of the dam reaches 532.7 ML, and the remaining water after irrigation is 518.4 ML. The amount of water in the dam increases after the start of the pumps and decreases during irrigation. The total amount of water pumped plus rainfall supplementation can satisfy the total amount of water demand. Meanwhile, the total amount of pumped water is 1,338 ML, which is also within the limit of 1,500 ML for maximum water usage permission. Therefore, the irrigation and water pum** model can be verified to suit the irrigation system, and the total energy consumption of the pumps also satisfies the irrigation demand.
In this study, we define the Baseline Case as the current energy system at the cotton farm which does not have RESs, and the required energy is supplied by the power grid only. Table 9 gives the comparison result between the Baseline Case and Optimal Case in terms of the MG components, investment cost, operation cost, and simple payback period. Optimal Case (\(\lambda _1\) = 0.6, \(\lambda _2\) = 0.2 and \(\lambda _3\) = 0.2) installed an MG and adopted TOU tariff and time-varying FIT in Eq. (4) to optimize the configuration. In addition, Optimal Case analyzes the importance of battery storage in the MG and how the battery systems store excess energy and sell it back to the grid to maximize the benefit. Figure 8 shows that RES generates electricity to supply the water pumps, but it does not have sufficient power to meet the pump load. Consequently, grid power is supplied to meet the shortage. Meanwhile, the MG system can sell excess power to the grid during off-peak irrigation since battery storage is an essential part of this study. Battery storage can support water pum** during the irrigation period and transfer the energy back to the grid during the off-peak period of irrigation. In the Optimal Case, it can be determined that the battery undergoes 288 charge cycles this year with a 100% DOD., the charge cycles of the battery are 288/3200 this year, which is 9% of the entire cycle life (3200) according to Table 7, the charge cycles of the battery are 288/3200 this year, which is 9% of the entire cycle life. Therefore, within the simple payback period of 9.49 years, there is no need to consider the cost of reinvesting in the battery. Furthermore, Fig. 9 shows the charging and discharging status of the battery over the year. The red bar is the excess energy charged to the battery storage from the MG. The magenta bars show that the battery storage provides energy to the pumps. During non-irrigation periods, the MG charges the battery storage and sells energy back to the grid when the PV stops generating power. Therefore, there are more benefits to choosing a time-varying FIT than using a flat-rate FIT. The brown bars in Fig. 9 show the scale of the battery selling energy to the grid during the year.
Sensitivity analyses
In this section, we conduct a sensitivity analysis and discuss the impact of different factors on the designed MG system.
Sensitivity 1: Impact of weighting coefficients
Here two scenarios are considered; in the first scenario, i.e., Scenario 1, choose the weighting factors to be \(\lambda _1=0.3\), \(\lambda _2=0.1\) and \(\lambda _3=0.6\). In Scenario 2, choose the weighting factors to be \(\lambda _1=0.2\), \(\lambda _2=0.6\) and \(\lambda _3=0.2\). The other system parameters remain intact as in the previous Optimal Case. The obtained results are shown in Table 10. By comparing the three results, \(\lambda _1=0.6\) in the Optimal Case has the highest preference for operation cost minimization, and the MG supplies the majority of the required energy, implying the smallest operation cost. Scenario 1 has \(\lambda _3=0.6\), i.e., the payback period has the highest weight, thus the obtained simple payback period is shorter than the Optimal Case. In Scenario 2, the weighting factor for investment is \(\lambda _2=0.6\); therefore, the optimization results show that the investment cost is lower, but the operation cost is higher than the Baseline Case and Scenario 1. Also, the simple payback period of Scenario 2 is the shortest in the three simulation cases. Figure 10 illustrates the comparison of Scenario 1 and Scenario 2 with the Optimal Case. Figure 11 shows the percentage of the MG components to meet the pum** load.
Sensitivity 2: Impact of different tariffs
Tariff selection is also a critical parameter affecting operating costs and simple payback periods. In this case, two types of tariff and two types of FIT based on the tariffs shown in Tables 2, 3 and 4 are adopted to see their effect on the MG configuration and simple payback period. Table 11 uses Baseline Case as a benchmark and lists the results of four tariff combinations. The operating cost of the case without MG is AU$ 49,694 under the TOU tariff and AU$ 44,277 under the flat rate tariff. It can be found from Table 11 that the shortest simple payback period is 8.15 years, and the smallest investment is AU$ 183,300 among the four tariff options. Table 11 also illustrates that if the operating cost is higher, the investment cost will be higher, but the simple payback period is shorter. If the operating cost is lower, the investment cost is relatively minor, but the simple payback period will be longer.
Sensitivity 3: Impact of wind speed and solar irradiation on the optimization microgrid system
WTs are one of the RESs mentioned in the previous section. The power generation of WTs changes significantly with wind speed. In the previous case study, the average wind speed of the case study cotton farm in 2016 was 3.42 m/s. The wind speed is scaled up to an average speed of 5 m/s to check the sensitivity of wind speed to the results, and all the parameters are kept the same as the Optimal Case. The relevant results are listed in the first column of Table 12. Under the condition of higher wind speed, this system has higher power generation, more investment cost and just 10 years payback period. The number of solar panels is increased from 242 units to 348 units, and the number of battery storage is increased from 10 to 20 sets. In addition, the number of battery charge cycles is 311, which is 9.7% of the entire battery cycle life, and there is no need to replace the battery in this case. Thus, the total investment cost is increased by AU$ 132,500. Moreover, the annual power generation is increased by 90,446 kWh. Compared with the Optimal Case, the operating cost is reduced from AU$ 21,612/year to AU$ 9,794/year, i.e., 54.7% reduction, and the corresponding simple payback period is increased by six more months. Now consider the impact of solar insolation, and it is assumed that the daily average global exposure is increased from 5.02 kWh/m\(^2\) to 6.0 kWh/m\(^2\) while the wind speed and all the other conditions remain the same as Optimal Case. The corresponding MG design results are listed in the second column of Table 12. Compared with the Optimal Case, the number of solar panels is increased by 3, and the number of batter units is increased by 4. Therefore, the total investment is decreased by AU$ 43,150. The annual power generation is increased by 28,390.61 kWh; thus, the operating cost is reduced by AU$ 3,709.6, and the payback period is 3 months longer. The number of battery charge cycles is 273, which is 8.5% of the entire battery cycle life; thus, no battery replacement cost is to be considered.
Sensitivity 4: Increased irrigation demand
Note that 33.33% of irrigation demand comes from rainfall from Table 1. However, the phenomenon of global warming is develo** rapidly, affecting the amount of rainfall and temperature of the world every year. We use a sensitivity analysis to model the impact of a reduction in rainfall from 33.33% to 15% due to climate change. Compared with the Baseline, when the rainfall is reduced by 18.33% and other conditions remain unchanged, it is equivalent to the need for pum** an additional 363.39 ML of water. Based on the relationship between water pum** and energy usage in Table 1, an additional 41,335 kWh of energy is required, which means the total energy demand is increased by 27.15%. Therefore, the total operational cost of the Baseline is changed to AU$ 63,186. Table 13 shows the optimization results of the increased irrigation demand case with two different MG configurations. In the same configuration as the Optimal Case, more energy is bought from the grid, and the operational cost is increased by AU$ 3,932; 8 more battery cycles are used. However, there is AU$37,642 saving, compared with the new Baseline operational cost; hence, the simple payback period is 7.08 years. On the other hand, the proposed model is used to re-configure the MG based on the water demand changes. To compare with the Optimal Case, the PV size is increased by 18.2 kW, and the number of batteries is reduced by 1 set; the investment cost is increased by AU$ 2,034, and the simple payback period is decreased by 2.44 years.
Conclusion
This paper presents an MG optimal design model for Australian cotton farms. This method formulates the design as a multi-objective optimization problem, which is subject to various constraints on PV, WT, battery storage, and cotton irrigation demand. In the 3 x 10\(^6\) m\(^2\) cotton farm case study, a number of different MG scenarios are presented to illustrate the effectiveness of the proposed model. Sensitivity analysis is also conducted to discuss the impact of weighting factors, battery storage and tariff options on the investment, operation cost and payback period. Compared with the existing energy consumption of this cotton farm, the designed MGs can reduce the operating costs by 44.16% to 56.51%, the simple payback periods are 8.35 years for Scenario 2 and 9.49 years for the Optimal Case, respectively. The grid-connected MG can also sell excess power to the grid to speed up the payback period. Additionally, the analysis of increased irrigation water demand illustrates the advantages of MG, especially as global warming impacts operational costs for the cotton farm; for example, the simple payback period is shortened from 9.49 years to 7.05 years. This case study provides a reference for cotton industry stakeholders to consider RES investment in cotton farms.
This study focuses only on grid-tied cotton farms while there are many cotton farms that are not grid-connected. Therefore, our future work will focus on the feasibility of MG design for those cotton farms where grid power is either limited or not available. We will also consider stochastic cases and compare the results with the deterministic approach under different availabilities of historical data.
Data Availability
The data supporting this study’s findings are available from the first author, Yunfeng Lin, upon reasonable request.
References
NSW Government (2014) Southern Cotton. https://www.industrynsw.gov.au/development/why-sydney-and-nsw/invest-case-studies/southern-cotton
Cotton Australia (2018) Australian cotton industry statistics. www.cottonaustralia.com.au
Lin Y, Wang J, Zhang J, Li L (2021) Optimal Investment Decision for Cotton Farm Microgrid Design. In 2021 31st Australasian Universities Power Engineering Conference (AUPEC), pages 1–6. https://doi.org/10.1109/AUPEC52110.2021.9597703
Powell JW, Welsh JM (2019) Integrating alternative Energy: A farm case study at Emerald, QLD
Powell JW, Welsh JM, Farquharson R (2019) Investment analysis of solar energy in a hybrid diesel irrigation pum** system in New South Wales, Australia. J Clean Prod 224:444–454
López-González A, Domenech B, Ferrer-Martí Laia (2018) Sustainability and design assessment of rural hybrid microgrids in Venezuela. Energy 159:229–242
Mariaud A, Acha S, Ekins-Daukes N, Shah N, Markides CN (2017) Integrated optimisation of photovoltaic and battery storage systems for UK commercial buildings. Appl Energy 199:466–478
Muh E, Tabet F (2019) Comparative analysis of hybrid renewable energy systems for off-grid applications in Southern Cameroons. Renew Energy 135:41–54
Kitson J, Williamson SJ, Harper PW, McMahon CA, Rosenberg G, Tierney MJ, Bell K, Gautam B (2018) Modelling of an expandable, reconfigurable, renewable DC microgrid for off-grid communities. Energy 160:142–153
Naderipour A, Saboori H, Mehrjerdi H, Jadid S, Abdul-Malek Z (2020) Sustainable and reliable hybrid AC/DC microgrid planning considering technology choice of equipment. Sustainable Energy, Grids and Networks 23:100386
Caballero F, Sauma E, Yanine F (2013) Business optimal design of a grid-connected hybrid PV (photovoltaic)-wind energy system without energy storage for an Easter Island’s block. Energy 61:248–261
Kumar J, Suryakiran BV, Verma A, Bhatti TS (2019) Analysis of techno-economic viability with demand response strategy of a grid-connected microgrid model for enhanced rural electrification in Uttar Pradesh state, India. Energy 178:176–185
Simply Energy (2019) Demand tariff. https://www.simplyenergy.com.au/business/electricity-and-gas/demand-tariff
Middelberg A, Zhang J, **a X (2009) An optimal control model for load shifting-with application in the energy management of a colliery. Appl Energy 86(7–8):1266–1273
Van Staden AJ, Zhang J, ** scheme with maximum demand charges. Appl Energy 88(12):4785–4794
Anvari-Moghaddam A, Rahimi-Kian A, Mirian MS, Guerrero JM (2017) A multi-agent based energy management solution for integrated buildings and microgrid system. Appl Energy 203:41–56
Chauhan RK, Phurailatpam C, Rajpurohit BS, Gonzalez-Longatt FM, Singh SN (2017) Demand-side management system for autonomous DC microgrid for building. Technol Econ Smart Grids Sustain Energy 2(1):1–11
El-Bidairi KS, Nguyen HD, Jayasinghe SDG, Mahmoud TS, Penesis I (2018) A hybrid energy management and battery size optimization for standalone microgrids: A case study for Flinders Island, Australia. Energy Convers Manag 175:192–212
Radosavljević J, Jevtić M, Klimenta D (2016) Energy and operation management of a microgrid using particle swarm optimization. Eng Optim 48(5):811–830
Lin X, Zamora R (2022) Controls of hybrid energy storage systems in microgrids: Critical review, case study and future trends. Journal of Energy Storage 47:103884
Shen Y, Hu W, Liu M, Yang F, Kong X (2022) Energy storage optimization method for microgrid considering multi-energy coupling demand response. Journal of Energy Storage 45:103521
Zhou K, Wei S, Yang S (2019) Time-of-use pricing model based on power supply chain for user-side microgrid. Appl Energy 248:35–43
Pallonetto F, Oxizidis S, Milano F, Finn D (2016) The effect of time-of-use tariffs on the demand response flexibility of an all-electric smart-grid-ready dwelling. Energy and Build 128:56–67
Ruppert M, Hayn M, Bertsch V, Fichtner W (2016) Impact of residential electricity tariffs with variable energy prices on low voltage grids with photovoltaic generation. Int J Electr Power Energy Syst 79:161–171
Azizivahed A, Barani M, Razavi S-E, Ghavidel S, Li L, Zhang J (2018) Energy storage management strategy in distribution networks utilised by photovoltaic resources. IET Generation, Transmission & Distribution 12(21):5627–5638
Williams NJ, Jaramillo P, Taneja J (2018) An investment risk assessment of microgrid utilities for rural electrification using the stochastic techno-economic microgrid model: A case study in Rwanda. Energy for Sustainable Development 42:87–96
Gan LK, Shek JKH, Mueller MA (2015) Hybrid wind-photovoltaic-diesel-battery system sizing tool development using empirical approach, life-cycle cost and performance analysis: A case study in Scotland. Energy Conversion and Management 106:479–494
Ma T, Yang H, Lu L, Peng J (2015) Pumped storage-based standalone photovoltaic power generation system: Modeling and techno-economic optimization. Appl Energy 137:649–659
Lofberg J (2004) YALMIP: A toolbox for modeling and optimization in MATLAB. In 2004 IEEE international conference on robotics and automation (IEEE Cat. No. 04CH37508), pages 284–289. IEEE
Australia Government Clean Energy Regulator (2019) "Small-scale systems eligible for certificates". http://www.cleanenergyregulator.gov.au/RET/Scheme-participants-and-industry/Agents-and-installers/Small-scale-systems-eligible-for-certificates
Roth G, Harris G, Gillies M, Montgomery J, Wigginton D (2013) Water-use efficiency and productivity trends in Australian irrigated cotton: a review. Crop and Pasture Science 64(12):1033–1048
NSW Department of Primary Industries (2016) Example Irrigated Farm Water Use Efficiency Assessment (IFWUEA). http://www.dpi.nsw.gov.au/
Cotton Research and Development Corporation (2012) WATERpak - a guide for irrigation management in cotton and grain farming systems. https://www.cottoninfo.com.au/sites/default/files/documents/WATERpak.pdf
Flores G, Hoffmann D, Rostron L, Shorten P (2017) VSDs lead irrigation efficiency measures for Gunnedah crop** enterprise. https://www.pumpindustry.com.au/vsds-lead-irrigation-efficiency-measures-for-gunnedah-crop**-enterprise/
CottonInfo (2015) Energy Case study - Energy-efficiency plan pays off for Gunnedah irrigator. https://www.cottoninfo.com.au/sites/default/files/documents/WATERpak.pdf
NASA Surface meteorology (2019) NASA Surface meteorology and Solar Energy database. https://power.larc.nasa.gov/data-access-viewer/
Energysage (2023) Tesla Powerwall 2. https://www.energysage.com/solar-batteries/tesla/6/powerwall-2/
Acknowledgements
This study is supported by an Australian Government Research Training Program Scholarship and funding from the Cotton Research and Development Corporation (CRDC).
Author information
Authors and Affiliations
Corresponding author
Ethics declarations
Disclosure statement
No potential conflict of interest was reported by the authors.
Additional information
Publisher's Note
Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Rights and permissions
Springer Nature or its licensor (e.g. a society or other partner) holds exclusive rights to this article under a publishing agreement with the author(s) or other rightsholder(s); author self-archiving of the accepted manuscript version of this article is solely governed by the terms of such publishing agreement and applicable law.
About this article
Cite this article
Lin, Y., Wang, J., Zhang, J. et al. Microgrid Optimal Investment Design for Cotton Farms in Australia. Smart Grids and Energy 9, 5 (2024). https://doi.org/10.1007/s40866-023-00184-z
Received:
Accepted:
Published:
DOI: https://doi.org/10.1007/s40866-023-00184-z